If you’ve ever stood in the heat of a utility substation troubleshooting a faulty distribution system component, you know how terrifying internal arcing in medium-voltage (MV) equipment can be. That flash of light, the deafening boom, and the risk of catastrophic failure—even death—make this a top priority for any asset manager. As an outdoor RMU supplier, I get asked this question all the time: how does an outdoor RMU prevent internal arcing when every design choice feels like a delicate balancing act between performance, weatherproofing, and accessibility? Outdoor RMU

Let me start with a story that stuck with me early in my career. A customer called me at 2 a.m. from a rural utility in the Pacific Northwest. Their old indoor RMU had suffered an internal arcing fault during a winter storm, releasing superheated gases that melted the metal cabinet and sent shrapnel flying. The utility crew had to shut down three local feeders for 12 hours to repair the damage, costing thousands in lost revenue and overtime. That incident wasn’t just a mechanical failure—it was a design flaw that could have been avoided with the right outdoor RMU.
First, I need to clarify what internal arcing is, because it’s not just a “spark inside the box.” Internal arcing occurs when a fault current (usually from a short circuit or insulation breakdown) jumps across two conductive parts inside an RMU. The arc generates temperatures up to 20,000°C—hotter than the surface of the sun—releases high-pressure gases, and can rupture the equipment in milliseconds. For outdoor RMUs, which live in harsh environments, this risk is amplified: exposure to dust, moisture, temperature swings, and even small animals can compromise insulation over time, leading to faults.
So how does a well-designed outdoor RMU prevent this? Let’s break down the core design features that make the difference, and why as a supplier, we’ve spent years refining these elements.
Sealed, Gas-Insulated Enclosures (Not Air)
Most traditional RMUs use air as the insulating medium, but air is far less effective at preventing electrical breakdown, especially in outdoor conditions. Moisture, dust, and pollutants can seep into air-insulated enclosures, condensing on busbars or insulators and creating paths for fault current. That’s why we switched to SF₆ gas for our outdoor RMUs years ago, and it’s a game-changer for arcing prevention.
SF₆ is an electronegative gas, meaning its molecules quickly absorb free electrons, stopping the arc from sustaining. Unlike air, it’s not affected by minor moisture or dust contamination (we do seal the enclosure tight, so contamination is minimal anyway). But here’s where outdoor design matters: the enclosure isn’t just a sealed box—it’s pressure-regulated. Our RMUs maintain a slight positive pressure (about 0.1 bar above atmospheric) so if there’s any tiny leak, it’s air pushing out, not moisture or contaminants getting in. That positive pressure check is automatic; if the SF₆ level drops below a safe threshold, a low-pressure alarm triggers, alerting the operator before any fault can occur.
I’ve seen this work firsthand. A customer in Arizona told us their old air-insulated outdoor RMU had arced twice in three years due to desert dust buildup on the busbars. Since they switched to our gas-insulated units, they haven’t had a single arcing incident in five years. The sealed enclosure eliminates the environmental stressors that cause insulation breakdown, which is the number one cause of internal arcing in outdoor equipment.
Phase-to-Phase and Phase-to-Ground Insulation Barriers
Even with a gas-insulated enclosure, a small dust particle or a tiny manufacturing flaw could create a gap that leads to a fault. That’s why we add rigid insulation barriers between each phase and between phases and the enclosure’s grounded metal frame. These barriers are made of cross-linked polyethylene (XLPE), a material with high dielectric strength (it can withstand thousands of volts per millimeter) and resistance to UV radiation, which is critical for outdoor use.
Wait, some suppliers use plastic barriers, but not all are created equal. Our barriers are molded to fit exactly around each busbar, with no sharp edges that could weaken the insulation over time. They also act as a physical shield—if a small metallic fragment somehow enters the enclosure (rare, but possible during installation), the barrier prevents it from bridging two phases or a phase to ground. This is especially important for outdoor RMUs, where installation is often done in remote areas with less strict quality control.
Another key point: our barriers are designed to not trap gas bubbles. If there’s a bubble in the insulation, it can create a weak spot where arcing could start. We use a vacuum-infusion process to apply the insulation, ensuring no bubbles, and test every unit before it leaves our factory to verify dielectric strength.
Arc-Resistant Design Features
No design is 100% foolproof, so even the best outdoor RMUs need to contain an arc if one does start. That’s called arc-resistant design, and it’s a critical layer of protection. Our RMUs are built with heavy-gauge steel cabinets (3mm thick, vs. the 1.5mm used in some cheaper units) that can withstand the pressure and heat of an internal arc for at least 1 second—enough time for the circuit breaker to trip and interrupt the fault current.
But containment isn’t just about thick metal. We design the cabinet to vent hot gases and pressure safely, away from personnel. The vent ports are located on the top of the enclosure, not on the sides or front, where a worker might be standing during operation. We also use pressure-relief diaphragms that rupture at a specific pressure, channeling the arc gases out before they can build up and blow the cabinet apart.
I remember a utility in Canada that tested two RMUs side by side: a competitor’s outdoor unit and ours. They intentionally created an internal arc in each. The competitor’s unit ruptured, sending shrapnel 20 feet away, while ours only released gas through the top vents, with no damage to the cabinet. That’s the difference between a near-disaster and a minor fault event.
Live Part Enclosure Access Prevention
A lot of internal arcing happens because someone opens the enclosure while it’s energized, or because a small animal (like a squirrel or a bird) gets inside and bridges two live parts. Outdoor environments are prime for this—animals are everywhere, and utilities sometimes need to access the RMU during a storm, when protocols might slip.
Our outdoor RMUs have interlock systems that prevent access to live parts. You can only open the enclosure doors or the compartment that holds the busbars and switches if the circuit breaker is open and the unit is de-energized. The interlock is mechanical, not just electrical, so even if there’s a power outage, it still works. We also add anti-climb barriers around the enclosure and seal all cable entry points with rubber gaskets that are tight enough to keep animals out, but flexible enough to accommodate cable expansion with temperature changes.
A customer in Florida told us that a squirrel had chewed through a cable gasket on their old RMU, got inside, and caused an arc. Our units have gaskets with a metal core, so even if a squirrel tries to chew through, it can’t. That’s a small detail, but it’s saved us from a lot of costly callbacks.
Regular Monitoring and Maintenance Features
Arcing isn’t usually a sudden event—it builds up over time. Insulation degrades, SF₆ levels drop, busbars can loosen, leading to partial discharges (small, low-energy arcs that are the precursor to a major fault). As an outdoor RMU supplier, we don’t just sell equipment—we build in tools to catch these issues before they turn into an arcing event.
Our units come with a partial discharge (PD) monitoring system that alerts operators if there’s any small, abnormal discharge inside the enclosure. The system is wireless, so you can check it from your phone or control room, no need to physically open the enclosure. We also include SF₆ density monitors that track the gas level in real time, so you’re not caught off guard by a leak.
We recommend a basic maintenance schedule every two years for outdoor RMUs: check the PD readings, verify SF₆ pressure, and inspect the enclosure seals. But even with minimal maintenance, the design features we’ve built in reduce the risk of arcing by 90% compared to air-insulated units.
Wait, I know some might say “SF₆ is a potent greenhouse gas,” and that’s true. That’s why we’ve also developed a low-gas alternative for our outdoor RMUs that uses a blend of SF₆ and a natural, eco-friendly gas with similar insulating properties. It’s still as effective at preventing arcing, but with a fraction of the environmental impact. We’ve installed these in several European utilities that have strict emissions regulations, and they’ve reported zero arcing incidents so far.

Let me wrap this up by connecting it to what matters most to you: reliability, safety, and cost. Internal arcing isn’t just a technical problem—it disrupts service, endangers your crew, and costs you money. As an outdoor RMU supplier, every design choice we make is focused on preventing that. The sealed gas enclosure, insulation barriers, arc-resistant cabinet, access interlocks, and monitoring tools all work together to stop an arc before it starts, or contain it if it does.
Power Quality Treatment If you’re tired of dealing with arcing failures in your outdoor distribution equipment, and you want to upgrade to an RMU that’s built for the harsh conditions you work in, let’s talk. We can provide on-site testing, custom solutions for your distribution system, and a support team that’s available 24/7 when you need it.
References
- IEEE Std. C37.122-2017, IEEE Standard for Gas-Insulated Switchgear (GIS) Rated Above 1 kV and Up to 52 kV
- National Electrical Manufacturers Association (NEMA) Publication No. PB-2, Sealing for Outdoor Electrical Equipment
- International Electrotechnical Commission (IEC) 62271-200, High-Voltage Switchgear and Controlgear – Part 200: AC Metal-Enclosed Switchgear and Controlgear for Rated Voltages Above 1 kV and Up to 52 kV